Figure 6-86 Querying the total electrical energy of system IT load output
4. Calculate the PUE of the smart module. PUE = Increment in total system input
electrical energy/Increment in total electrical energy of system IT load output
= 10.0 kWh/6.0 kWh = 1.67.
6.8.2 Configuring PUE User-defined Mode
Context
This section describes how to configure PUE for the integrated PDU connected.
The functions of configuration buttons for the PUE user-defined mode are
described as follows.
Table 6-51 PUE configuration buttons
No.
Button
Description
1
Add
Adds new total power consumption or IT power consumption
parameters.
2
Delete
Deletes a parameter setting for the total power consumption
or IT power consumption.
Procedure
Step 1 Log in to the ECC800-Pro WebUI as an administrator.
Step 2 Choose System Settings > PUE Configuration.
Step 3 Set PUE function to Enable.
Step 4 Set PUE configuration mode to User-defined, and click Submit.
1. On the Total Power Consumption Configuration tab page, click Add to
enter the Total Power Consumption Configuration page. On the Select
Device tab page, select Integrated PDU 1. On the Select Indicators tab
page, select Total active electricity energy of PDU input, and click Confirm.