Table 8-6 Adding a transformer
Path
Parameter
Setting
Choose
System
Settings >
Device
Management
and click Add
Device. The
parameters
for adding
devices are
displayed.
Device
attribute
Select Transformer from the drop-down
list box.
Device Type
Select Transformer_LD-B10 from the
drop-down list box.
Connect To
Select ECC800 from the drop-down list
box.
Communicati
ons Port
Select COM1 from the drop-down list box.
Device
Address
In this example, Device Address is set to 1.
During actual configuration, set the device
address for the transformer based on the
actual situation.
3. Click Test Connect to check whether the transformer is properly connected to
the ECC800-Pro.
–
If the connection succeeds, click Confirm. The connected devices are
displayed in the Number of connected devices list.
–
If the connection fails, check whether the device is properly connected to
the ECC800-Pro, whether the device and ECC800-Pro are running
properly, and whether the parameter settings are consistent with the
device parameters.
----End
8.7.8 How Can I Set and Add an SVG-In-Power (Modbus-RTU)?
Prerequisites
One end of the straight-through cable has been connected to pins 4 and 9 of the
COM port on the SVG display, and the other end has been connected to the COM
port on the ECC800-Pro.
NO TE
Pin 4 defines 485+, and pin 9 defines 485–.
Procedure
Step 1 Set SVG display parameters.
1. Tap Expert Setting. On the displayed SVG communication settings screen, set
ID to 1 and Baud to 9600.
NO TE
ID is the communication address, ranging from 1 to 255. This operation uses 1 as an
example.
ECC800 Data Center Controller
User Manual
8 FAQ
Issue 04 (2021-10-09)
Copyright © Huawei Technologies Co., Ltd.
310