----End
8.7.36 How Can I Commission a Temperature Sensor
(Connected to the NTC Port on the T/H Sensor)?
If a temperature sensor is installed, perform the following steps to configure it.
Prerequisites
Cables have been connected to the NTC, T/H sensor, and UIM20A expansion
module.
Figure 8-16 Wiring diagram
(1) UIM20A expansion module (2) T/H sensor
(3) Temperature sensor
Procedure
Step 1 The NTC port on the T/H sensor connected to the temperature sensor supports
automatic identification. Therefore, you do not need to set parameters.
Step 2 Add the T/H sensor.
1. Log in to the ECC800-Pro WebUI as an administrator.
2. Add the T/H sensor.
Choose System Settings > Device Management and click Auto Discover
Device to add the T/H sensor. The device connection information is displayed.
ECC800 Data Center Controller
User Manual
8 FAQ
Issue 04 (2021-10-09)
Copyright © Huawei Technologies Co., Ltd.
347