NO TE
After the corresponding AI/DI device is enabled, the AI/DI device type must be
consistent with the DO state.
Table 6-39 Fire sensor NO and NC definitions
Item
Definition
NO
Dry contact signal for the fire sensor
abnormality alarm. Closed: alarm;
open: normal
NC
Dry contact signal for the fire sensor
abnormality alarm. Closed: normal;
open: alarm
4. Click Submit.
----End
Follow-up Procedure
After the alarm has been cleared when fire control linkage or smoke alarm
linkage occurs, perform the following operations:
●
Close the skylight manually.
●
Start the smart cooling products manually.
●
After turning off the lights, set Set light mode of the AC actuator to
Automatic. WebUI path: Monitoring > Aisle > AC Actuator Group > AC
Actuator > Running Parameters.
NO TE
When a smart module actuator is configured, you need to set parameters for the
smart module actuator. The setting process is similar.
6.6.1.2 High Temperature Linkage
Context
●
The ECC800-Pro implements high temperature linkage. If it detects high
temperature alarms by interacting with multi-functional sensors and all smart
cooling products fail to communicate with the ECC800-Pro, the ECC800-Pro
opens skylights based on the alarm status to facilitate heat dissipation.
●
The default status of high temperature linkage is off. Set it based on the
actual situation.
Procedure
Step 1 Log in to the ECC800-Pro WebUI as an administrator.
Step 2 Choose System Settings > Linkage Control.