Table 8-43 Description of communications parameters to be set on a device
Parameter
Recommended Value
Baud rate
This section uses 9600 as an example. Set this
parameter based on site requirements.
NOTE
For certain devices, this parameter does not need to be set.
Communications
address
This section uses 1 as an example. Set this parameter
based on site requirements.
Step 2 Add the device to the ECC800-Pro WebUI.
1. Log in to the ECC800-Pro WebUI as an administrator.
2. Add the device.
Table 8-44 Parameter description for adding a device
Path
Parameter
Setting
Choose
System
Settings >
Device
Management
and click Add
Device. The
parameters
for adding
devices are
displayed.
Device
attribute
Select the device attribute to be accessed
from the drop-down list box.
Device Type
Select the device type to be accessed from
the drop-down list box.
Connect To
Select the corresponding ETH converter
from the drop-down list box.
NOTE
Use the blinking function of the ETH converter
to identify the mapping between the device and
the ETH converter.
Communicati
ons Port
COM1/COM2
Device
Address
This section uses 1 as an example. In
practice, set this parameter to be the same
as the communications address for the
device.
3. Click Test Connect to check whether the device connects to the ECC800-Pro
properly.
–
If the connection succeeds, click Confirm. The connected devices are
displayed in the Number of connected devices list.
–
If the connection fails, check whether the device is properly connected to
the ECC800-Pro, whether the device and ECC800-Pro are running
properly, and whether the parameter settings are consistent with the
device parameters.
ECC800 Data Center Controller
User Manual
8 FAQ
Issue 04 (2021-10-09)
Copyright © Huawei Technologies Co., Ltd.