If the connection fails, check whether the device is properly connected to
the ECC800-Pro, whether the device and ECC800-Pro are running
properly, and whether the parameter settings are consistent with the
device parameters.
----End
8.7.14 How Can I Set and Add a DC Power Supply (Modbus-
RTU)?
Prerequisites
One end of the straight-through cable has been connected to the RS485 port on
the SMU02C in the MTS9604B-N20B1 cabinet, and the other end has been
connected to the COM port on the ECC800-Pro collector or ETH converter.
Procedure
Step 1 Connect the RS485 communications port on the SMU02C.
Figure 8-10 RS485 communications port
Step 2 Add a DC power supply.
1. Log in to the ECC800-Pro WebUI as an administrator.
2. Add a DC power supply.
Table 8-13 Adding a DC power supply
Path
Parameter
Setting
Choose
System
Settings >
Device
Management
and click Add
Device. The
parameters
for adding
devices are
displayed.
Device
attribute
Select a DC Power Source from the drop-
down list box.
Device Type
Select MTS9604B_MTS9606B Power
Supply from the drop-down list box.
Connect To
Select ECC800 from the drop-down list
box.
ECC800 Data Center Controller
User Manual
8 FAQ
Issue 04 (2021-10-09)
Copyright © Huawei Technologies Co., Ltd.
318