HV580L Series Frequency Inverter
88
Setting Range
0.01A
~
P1-
03(AC drive power ≤ 55kW)
0.1A
~
P1-03(AC drive power >55kW)
The parameters in P1-06 to P-10 are asynchronous motor parameters. These parameters are unavailable on
the motor nameplate and are obtained by means of motor auto-tuning. Only P1-06 to P1-08 can be obtained
through static motor auto-tuning. Through complete motor auto-tuning, encoder phase sequence and current
loop PI can be obtained besides the parameters in P1-06 to P1-10.
Each time "Rated motor power" (P1-01) or "Rated motor voltage" (P1-02) is changed; the AC drive
automatically restores values of P1-06 to P1-10 to the parameter setting for the common standard Y series
asynchronous motor.
If it is impossible to perform motor auto-tuning onsite, manually input the values of these parameters
according to data provided by the motor manufacturer.
P1-16
Stator resistance
(synchronous motor)
Default
Model dependent
Setting Range
0.001Ω
~
65.535Ω(AC drive power ≤ 55kW)
0.0001Ω
~
6.5535Ω(AC drive power >55kW)
P1-17
Shaft D inductance
(synchronous motor)
Default
Model dependent
Setting Range
0.01mH
~
655.35mH(AC drive power ≤ 55kW)
0.001mH
~
65.535mH(AC drive power >55kW)
P1-18
Shaft Q inductance
(synchronous motor)
Default
Model dependent
Setting Range
0.01mH
~
655.35mH(AC drive power ≤ 55kW)
0.001mH
~
65.535mH(AC drive power >55kW)
P1-20
Back EMF
(synchronous motor)
Default
Model dependent
Setting Range
0.1V
~
6553.5V
P1-16 to P-20 is synchronous motor parameters. These parameters are unavailable on the nameplate of most
synchronous motors and can be obtained by means of "Synchronous motor no-load auto-tuning". Through
"Synchronous motor with-load auto-tuning", only the encoder phase sequence and installation angle can be
obtained.
Each time "Rated motor power" (P1-01) or "Rated motor voltage" (P1-02) is changed; the AC drive
automatically modifies the values of P1-16 to P1-20.