HV580L Series Frequency Inverter
195
High byte: P0~PF (P group), A0~AF (A group), 70~7F (U group) Low byte: 00~FF
For example: P3.12, the address indicates 0xP30C
Caution:
Group PF: Parameters could not be read or be modified.
Group U: Parameters could be read but not be modified.
Some parameters can not be changed during operation; some parameters regardless of the kind of state the
inverter in, the parameters can not be changed. Change the function code parameters, pay attention to the
scope of the parameters, units, and relative instructions.
Besides, if EEPROM is frequently stored, it will reduce the service life of EEPROM. In some communication
mode, function code needn’t to be stored as long as changing the RAM value.
Group P: to achieve this function, change high order P of the function code address into 0.
Group A: to achieve this function, change high order A of the function code address to be 4.
Corresponding function code addresses are indicated below:
High byte
:
00~0F (P group), 40~4F (A group) Low byte: 00~FF
For example:
Function code P3.12 can not be stored into EEPROM, address indicates to be 030C, function code A0-05 can
not be stored in EEPROM, address indicates to be 4005; This address can only act writing RAM, it can not act
reading, when act reading, it is invalid address. For all parameters, command code 07H can be used to
achieve this function.
Stop/run parameters:
Parameter add.
Parameter description
Parameter
addr.
Parameter description
1000H
* Communication Setting value
(decimalism)
–10000
~
10000
1010H
PID setup
1001H
Running frequency
1011H
PID feedback
1002H
Bus voltage
1012H
PLC process
1003H
Output voltage
1013H
PULSE input pulse frequency, unit
0.01kHz
1004H
Output current
1014H
Feedback speed, unit 0.1Hz
1005H
Output power
1015H
Rest running time
1006H
Output torque
1016H
AI1 voltage before correction
1007H
Running speed
1017H
AI2 voltage before correction