HV580L Series Frequency Inverter
62
Function
Code
Parameter Name
Setting Range
Default
Property
P9-49
Fault protection action
selection 3
Unit's digit (User-defined fault 1, Err27)
0: Coast to stop
1: Stop according to the stop mode
2: Continue to run
Ten's digit (User-defined fault 2, Err28)
0: Coast to stop
1: Stop according to the stop mode
2: Continue to run
Hundred's digit (Accumulative power-on
time reached, Err29)
0: Coast to stop
1: Stop according to the stop mode
2: Continue to run
Thousand's digit (Load becoming 0, Err30)
1: Coast to stop
2: Continue to run at 7% of rated motor
frequency and resume to the set frequency
if the load recovers
00000
☆
P9-50
Fault protection action
selection 4
Unit's digit (Too large speed deviation,
Err42)
0: Coast to stop
1: Stop according to the stop mode
2: Continue to run
Ten's digit (Motor over-speed, Err43)
Hundred's digit (Initial position fault, Err51)
00000
☆
P9-54
Frequency selection for
continuing to run upon fault
0: Current running frequency
1: Set frequency
2: Frequency upper limit
3: Frequency lower limit
4: Backup frequency upon abnormality
0
☆
P9-55
Backup frequency upon
abnormality
0.0%
~
100.0%
(100.0% maximum frequency P0-10)
100.0%
☆
P9-56
Type of motor temperature
sensor
0: No temperature sensor
1: PT100 2: PT1000
0
☆