value of this parameter.
The output frequency of the HV580L can reach up to 3200 Hz. To take both frequency reference resolution
and frequency input range into consideration, you can set the number of decimal places for frequency
reference in P0-22.
If P0-22 is set to 1, the frequency reference resolution is 0.1 Hz. In this case, the setting range of P0-10 is 50.0
to 3200.0 Hz.
If P0-22 is set to 2, the frequency reference resolution is 0.01 Hz. In this case, the setting range of P0-10 is
50.00 to 320.00 Hz.
P0-11
Source of frequency
upper limit
Default
0
Setting Range
0
Set by P0-12
1
VS
2
AS
3
VS2
4
PULSE setting (X5)
5
Communication setting
It is used to set the source of the frequency upper limit, including digital setting (P0-12), AI, pulse setting or
communication setting. If the frequency upper limit is set by means of analog input, the analog input setting is
100% corresponding to P0-12.
For example, to avoid runaway in torque control mode in winding application, you can set the frequency upper
limit by means of analog input. When the AC drive reaches the upper limit, it will continue to run at this speed.
P0-12
Frequency upper limit
Default
50.00Hz
Setting Range
Frequency lower limit P0-14
~
maximum frequency P0-10
P0-13
Frequency upper limit
offset
Default
0.00Hz
Setting Range
0.00Hz
~
maximum frequency P0-10
If the source of the frequency upper limit is analog input or pulse setting, the final frequency upper limit is
obtained by adding the offset in this parameter to the frequency upper limit set in P0-11
P0-14
Frequency lower limit
Default
0.00Hz
Setting Range
0.00Hz
~
frequency upper limit P0-12
If the frequency reference is lower than the value of this parameter, the AC drive can stop, run at the
frequency lower limit, or run at zero speed, determined by P8-14.
P0-15
Carrier frequency
Default
Model dependent
Setting Range
0.5kHz
~
16.0kHz