It is applicable to scenarios where complete auto-tuning cannot be performed because the asynchronous
motor cannot be disconnected from the load.
Before performing static auto-tuning, properly set the motor type and motor nameplate parameters of P1-00 to
P1-05 first. The AC drive will obtain parameters of P1-06 to P1-08 by static auto-tuning.
Action specification: Set this parameter to 1, and press the RUN key. Then, the AC drive starts static
auto-tuning.
2: Asynchronous motor complete auto-tuning
To perform this type of auto-tuning, ensure that the motor is disconnected from the load. During the process of
complete auto-tuning, the AC drive performs static auto-tuning first and then accelerates to 80% of the rated
motor frequency within the acceleration time set in P0-17. The AC drive keeps running for a certain period and
then decelerates to stop within deceleration time set in P0-18.
Before performing complete auto-tuning, properly set the motor type, motor nameplate parameters of P1-00 to
P1-05, "Encoder type" (P1-28) and "Encoder pulses per revolution" (P1-27) first.
The AC drive will obtain motor parameters of P1-06 to P1-10, "A/B phase sequence of ABZ incremental
encoder" (P1-30) and vector control current loop PI parameters of P2-13 to P2-16 by complete auto-tuning.
Action specification: Set this parameter to 2, and press the RUN key. Then, the AC drive starts complete auto
tuning.
3: Static complete parameter identification
Suitable for no encoder, motor under stationary state to complete motor parameter self learning (the motor
may be still slight shaking, need to pay attention to safety).
Before complete asynchronous machine static tuning, the motor type and motor nameplate parameter P1-00
~ P1-05 must be set properly. After complete asynchronous machine static tuning, frequency inverter can get
P1-06 ~ P1-10 five parameters
11: Synchronous motor with-load auto-tuning
It is applicable to scenarios where the synchronous motor cannot be disconnected from the load. During
with-load auto-tuning, the motor rotates at the speed of 10 PRM.
Before performing with-load auto-tuning, properly set the motor type and motor nameplate parameters of
P1-00 to P1-05 first.
By with-load auto-tuning, the AC drive obtains the initial position angle of the synchronous motor, which is a
necessary prerequisite of the motor's normal running.
Before the first use of the synchronous motor after installation, motor auto-tuning must be performed.
Action specification: Set this parameter to 11, and press the RUN key. Then, the AC drive starts with-load