HV580L Series Frequency Inverter
101
Pulse setting specification: voltage range 9
–30 V, frequency range 0–100 kHz
5: Multi-reference
If the voltage source is multi-reference, parameters in group P4 and PC must be set to determine the
corresponding relationship between setting signal and setting voltage.
6: Simple PLC
If the voltage source is simple PLC mode, parameters in group PC must be set to determine the setting output voltage.
7: PID
The output voltage is generated based on PID closed loop. For details, see the description of PID in group PA.
8: Communication setting
The output voltage is set by the host computer by means of communication.
When the voltage source to choose 1 ~ 8, 0 ~ 100% are corresponding to the output voltage of 0 V~ motor
rated voltage.
P3-14
VF Separation of digital
voltage setting
Default
0V
Setting Range
0V
~
Motor Rated Voltage
P3-15
Voltage rise time of VF
separation
Default
0.0s
Setting Range
0.0s
~
1000.0s
P3-15
Voltage decline time of
VF separation
Default
0.0s
Setting Range
0.0s
~
1000.0s
The voltage source for VF separation is set in the same way as the frequency source. For details, see P0-03.
100.0% of the setting in each mode corresponds to the rated motor voltage. If the corresponding value is
negative, its absolute value is used
P3-15 indicates the time required for the output voltage to rise from 0 V to the rated motor voltage shown as t1
in the following figure.
P3-16 indicates the time required for the output voltage to decline from the rated motor voltage to 0 V, shown
as t2 in the following figure.