HV580L Series Frequency Inverter
130
If a parameter needs to be displayed during the running, set the
corresponding bit to 1, and set P7-05 to the hexadecimal equivalent of
this binary number.
P7-06
Load speed display coefficient
Default
1.0000
Setting Range
0.0001
~
6.5000
This parameter is used to adjust the relationship between the output frequency of the AC drive and the load
speed. For details, see the description of P7-12.
P7-07
Heatsink temperature of inverter Module Default
-
Setting Range
0.0
℃~
100.0
℃
It is used to display the insulated gate bipolar transistor (IGBT) temperature of the inverter module, and the
IGBT overheat protection value of the inverter module depends on the model.
P7-08
Temporary software version
Default
-
Setting Range
–
It is used to display the temporary software version of the control board.
P7-09
Accumulative running time
Default
0 hour
Setting Range
0h
~
65535h
It is used to display the accumulative running time of the AC drive. After the accumulative running time
reaches the value set in P8-17, the terminal with the digital output function 12 becomes ON.
P7-10
Product number
Default
Setting Range
AC drive product number
P7-11
Software version
Default
Setting Range
Software version of control board
P7-12
Number of decimal places for
load speed
display
Default
1
Setting Range
0
0 decimal place
1
1 decimal place
2
2 decimal places
3
3 decimal places
P7-12 is used to set the number of decimal places for load speed display. The following gives an example to
explain how to calculate the load speed:
Assume that P7-06 (Load speed display coefficient) is 2.000 and P7-12 is 2 (2 decimal places). When the
running frequency of the AC drive is 40.00 Hz, the load speed is 40.00 x 2.000 = 80.00 (display of 2 decimal
places).