HV580L Series Frequency Inverter
64
Function
Code
Parameter Name
Setting Range
Default
Property
Group PA: Process Control PID Function
PA-00
PID setting source
0: PA-01 setting
1: VS
2: AS
3: VS2
4: PULSE setting (X5)
5: Communication setting
6: Multi-reference
0
☆
PA-01
PID digital setting
0.0%
~
100.0%
50.0%
☆
PA-02
PID feedback source
0: VS
1: AS
2: VS2
3: VS-AS
4: PULSE setting (X5)
5: Communication setting
6: VS+AS
7: MAX(|VS|, |AS|)
8: MIN(|VS|, |AS|)
0
☆
PA-03
PID action direction
0: Forward action
1: Reverse action
0
☆
PA-04
PID setting feedback range
0
~
65535
1000
☆
PA-05
Proportional gain Kp1
0.0
~
100.0
20.0
☆
PA-06
Integral time Ti1
0.01s
~
10.00s
2.00s
☆
PA-07
Differential time Td1
0.000s
~
10.000s
0.000s
☆
PA-08
Cut-off frequency of PID reverse
rotation
0.00
~
maximum frequency
2.00Hz
☆
PA-09
PID deviation limit
0.0%
~
100.0%
0.0%
☆
PA-10
PID differential limit
0.00%
~
100.00%
0.10%
☆
PA-11
PID setting change time
0.00
~
650.00s
0.00s
☆
PA-12
PID feedback filter time
0.00
~
60.00s
0.00s
☆