HV580L Series Frequency Inverter
180
Power output
phase loss
Err13
1: The cable connecting the AC drive and
the motor is faulty.
2: The AC drive's three-phase outputs are
unbalanced when the motor is running.
3: The drive board is faulty.
4: The module is faulty.
1: Eliminate external faults.
2: Check whether the motor
three-phase winding is normal.
3: Contact the agent or HNC
Electric.
Module overheat Err14
1: The ambient temperature is too high.
2: The air filter is blocked.
3: The fan is damaged.
4: The thermally sensitive resistor of the
module is damaged.
5: The inverter module is damaged.
1: Lower the ambient temperature.
2: Clean the air filter.
3: Replace the damaged fan.
4: Replace the damaged thermally
sensitive resistor.
5: Replace the inverter module.
External
equipment fault
Err15
1: External fault signal is input via DI.
2: External fault signal is input via virtual I/O.
Reset the operation.
Communication
fault
Err16
1: The host computer is in abnormal state.
2: The communication cable is faulty.
3: P0-28 is set improperly.
4: The communication parameters in group
PD are set improperly.
1: Check the cabling of host
computer.
2: Check the communication
cabling.
3: Set P0-28 correctly.
4: Set the communication
parameters properly
Contactor fault
Err17
1: The drive board and power supply are
faulty.
2: The contactor is faulty.
1: Replace the faulty drive board or
power supply board.
2: Replace the faulty contactor.
Current detection
fault
Err18
1: The HALL device is faulty.
2: The drive board is faulty.
1: Replace the faulty HALL device.
2: Replace the faulty drive board.
Fault Name