HV580L Series Frequency Inverter
168
1: Restore default settings except motor parameters
If PP-01 is set to 1, most function codes are restored to the default settings except motor parameters,
frequency reference resolution (P0-22), fault records, accumulative running time (P7-09), accumulative
power-on time (P7-13) and accumulative power consumption (P7-14).
2: Clear records
If PP-01 is set to 2, the fault records, accumulative running time (P7-09), accumulative power-on time (P7-13)
and accumulative power consumption P7-14) are cleared.
501: Back up current user parameters
If PP-01 is set to 501, the current parameter settings are backed up, helping you to restore the setting if
incorrect parameter setting is performed.
4: Restore user backup parameters
If PP-01 is set to 4, the previous backup user parameters are restored.
PP-02
AC drive parameter
display property
Default
11
Setting
range
Unit's digit Group U display selection
0
No display
1
Display
Ten's digit
Group A display selection
0
No display
1
Display
PP-03
Individualized parameter
display property
Default
00
Setting
range
Unit's digit User-defined parameter display selection
0
No display
1
Display
Ten's digit
User-modified parameter display selection
0
No display
1
Display
The setting of parameter display mode aims to facilitate you to view different types of parameters based on
actual requirements. The HV580L provides the following three parameter display modes.