HV580L Series Frequency Inverter
146
P9-34
Bus voltage upon 2nd fault
P9-37
X terminal status upon 1st fault
Same as P9-17
~
P9-24
P9-38
Current upon 1st fault
P9-39
Bus voltage upon 3rd fault
P9-40
X terminal status upon 1st fault
P9-41
Output terminal status
upon 1st fault
P9-42
AC Drive status upon 1
st
fault
P9-43
Output terminal status upon 1st
fault
P9-44
Frequency upon 1st fault
P9-47
Fault protection action selection 1
Default
00000
Setting Range
Unit's digit
Motor overload (Err11)
0
Coast to stop
1
Stop according to the stop mode
2
Continue to run
Ten's digit
Power input phase loss (Err12)
(Same as unit's digit)
Hundred's digit
Power output phase loss (Err13)
(Same as unit's digit)
Thousand's digit
External equipment fault (Err15)
(Same as unit's digit)
Ten thousand's digit
Communication fault (Err16)
(Same as unit's digit)
P9-48
Fault protection action selection 2
Default
00000
Setting Range
Unit's digit
Encoder fault (Err20)
0
Coast to stop
1
Switch over to V/F control, stop according to the
stop mode