HV580L Series Frequency Inverter
148
P9-50
Fault protection action selection 4
Default
00000
Setting Range
Unit's digit
Too large speed deviation, (Err42)
Same as unit's digit in P9-47
Ten's digit
Motor over-speed (Err43)
Same as unit's digit in P9-47
Hundred's digit
Initial position fault (Err51)
Same as unit's digit in P9-47
Thousand's digit
Speed feedback fault (Err52)
Same as unit's digit in P9-47
Ten thousand's digit
Reserved
If "Coast to stop" is selected, the AC drive displays Err** and directly stops.
• If "Stop according to the stop mode" is selected, the AC drive displays A** and stops according to the stop
mode. After stop, the AC drive displays Err**.
• If "Continue to run" is selected, the AC drive continues to run and displays A**. The running frequency is set
in P9-54.
P9-54
Frequency selection for
continuing to run upon fault
Default
0
Setting Range
0
Current running frequency
1
Set frequency
2
Frequency upper limit
3
Frequency lower limit
4
Backup frequency upon abnormality
P9-55
Backup frequency upon
abnormality
Default
100.0%
Setting Range
0.0%
~
100.0%(maximum frequency)
If a fault occurs during the running of the AC drive and the handling of fault is set to "Continue to run", the AC
drive displays A** and continues to run at the frequency set in P9-54.
The setting of F9-55 is a percentage relative to the maximum frequency.