HV580L Series Frequency Inverter
120
33
Reverse running
If the AC drive is in the reverse running state, the terminal
becomes ON.
34
Zero current state
Refer to the descriptions of P8-28 and P8-29.
35
Module temperature
reached
If the heatsink temperature of the inverter module (P7-07)
reaches the set module temperature threshold (P8-47),
the terminal becomes ON.
36
Software current limit
exceeded
Refer to the descriptions of P8-36 and P8-37.
37
Frequency lower limit reached
(having output at stop)
If the running frequency reaches the lower limit, the terminal
becomes ON. In the stop state, the signal is still ON.
38
Alarm output
If a fault occurs on the AC drive and the AC drive
continues to run, the terminal outputs the alarm signal.
39
Motor overheat
warning
If the motor temperature reaches the temperature set in
P9-58 (Motor overheat warning threshold), the terminal
becomes ON. You can view the motor temperature by
using U0-34.
40
Current running time
reached
If the current running time of AC drive exceeds the value
of P8-53, the terminal becomes ON
P5-06
Y2P function selection (Pulse output terminal)
Default
0
P5-07
AO1 function selection
Default
0
P5-08
AO2 function selection
Default
1
The output pulse frequency of the Y2P terminal ranges from 0.01 kHz to "Maximum Y2P output frequency"
(P5-09). The value of P5-09 is between 0.01 kHz and 100.00 kHz.
The output range of AO1 and AO2 is 0
–10 V or 0–20 mA.
The relationship between pulse and analog output ranges and corresponding functions is listed in the
following table.
Value
Function
Range (Corresponding to Pulse or Analog Output
Range 0.0%
–100.0%)
0
Running frequency
0 to maximum output frequency
1
Set frequency
0 to maximum output frequency
2
Output current
0 to 2 times of rated motor current
3
Output torque (absolute value)
0 to 2 times of rated motor torque
4
Output power
0 to 2 times of rated power
5
Output voltage
0 to 1.2 times of rated AC drive voltage
6
Pulse input
0.01kHz
~
100.00kHz