HV580L Series Frequency Inverter
107
50
Clear the current running
time
When this terminal becomes ON, the AC drive's current running
time is cleared. This function must be supported by P8-42 and
P8-53.
Appendix 1: State combinations of the four multi-reference terminals
The four multi-reference terminals have 16 state combinations, corresponding to 16 reference values, as listed
in the following table:
K4
K3
K2
K1
Reference Setting
Corresponding
Parameter
OFF
OFF
OFF
OFF
Reference 0
PC-00
OFF
OFF
OFF
ON
Reference 1
PC-01
OFF
OFF
ON
OFF
Reference 2
PC-02
OFF
OFF
ON
ON
Reference 3
PC-03
OFF
ON
OFF
OFF
Reference 4
PC-04
OFF
ON
OFF
ON
Reference 5
PC-05
OFF
ON
ON
OFF
Reference 6
PC-06
OFF
ON
ON
ON
Reference 7
PC-07
ON
OFF
OFF
OFF
Reference 8
PC-08
ON
OFF
OFF
ON
Reference 9
PC-09
ON
OFF
ON
OFF
Reference 10
PC-10
ON
OFF
ON
ON
Reference 11
PC-11
ON
ON
OFF
OFF
Reference 12
PC-12
ON
ON
OFF
ON
Reference 13
PC-13
ON
ON
ON
OFF
Reference 14
PC-14
ON
ON
ON
ON
Reference 15
PC-15
If the frequency source is multi-reference, the value 100% of PC-00 to PC-15 corresponds to the value of
P0-10 (Maximum frequency).
Besides the multi-speed function, the multi-reference can be also used as the PID setting source or the
voltage source for VF separation, satisfying the requirement on switchover of different setting values.
Appendix 2: State combinations of two terminals for acceleration/deceleration time selection
Terminal 2
Terminal 1
Acceleration/Deceleration Time
Selection
Corresponding Parameters
OFF
OFF
Acceleration/Deceleration time 1
P0-17
、
P0-18
OFF
ON
Acceleration/Deceleration time 2
P8-03
、
P8-04