HV580L Series Frequency Inverter
84
acceleration/deceleration time also change.
P0-21
Frequency offset of auxiliary
frequency source for X and Y
operation
Default
0.00Hz
Setting Range
0.00Hz
~
maximum frequency P0-10
This parameter is valid only when the frequency source is set to "X and Y operation".
The final frequency is obtained by adding the frequency offset set in this parameter to the X and Y operation result.
P0-22
Frequency reference
resolution
Default
2
Setting Range
1
0.1Hz
2
0.01Hz
It is used to set the resolution of all frequency-related parameters.
If the resolution is 0.1 Hz, the HV580L can output up to 3200 Hz. If the resolution is 0.01 Hz, the HV580L can
output up to 600.00 Hz.
Note:
Modifying this parameter will make the decimal places of all frequency-related parameters change and
corresponding frequency values change.
P0-23
Retentive of digital setting
frequency upon power failure
Default
0
Setting Range
0
Not retentive
1
Retentive
This parameter is valid only when the frequency source is digital setting.
If P0-23 is set to 0, the digital setting frequency value resumes to the value of P0-08 (Preset frequency) after
the AC drive
stops. The modification by using keys ▲ and ▼ or the terminal UP/DOWN function is cleared.
If P0-23 is set to 1, the digital setting frequency value is the set frequency at the moment when the AC drives
stops. The modification by using keys ▲ and ▼ or the terminal UP/DOWN function remains effective.
P0-24
Motor parameter group
selection
Default
0
Setting Range
0
Motor parameter group 1
1
Motor parameter group 2
2
Motor parameter group 3
3
Motor parameter group 4
The HV580L can drive four motors at different time. You can set the motor nameplate parameters respectively,