HV580L Series Frequency Inverter
55
Function
Code
Parameter Name
Setting Range
Default
Property
P8-21
Detection range of frequency
reached
0.0%
~
100.0% (maximum frequency)
0.0%
☆
P8-22
Jump frequency during
acceleration/deceleration
0: Disabled 1: Enabled
0
☆
P8-25
Frequency switchover point
between acceleration time 1
and acceleration time 2
0.00 Hz to maximum frequency
0.00Hz
☆
P8-26
Frequency switchover point
between deceleration time 1
and deceleration time 2
0.00 to maximum frequency
0.00Hz
☆
P8-27
Terminal JOG preferred
0: Disabled 1: Enabled
0
☆
P8-28
Frequency detection value
(PDT2)
0.00 to maximum frequency
50.00Hz
☆
P8-29
Frequency detection
hysteresis (PDT2)
0.0%
–100.0% (PDT2 level)
5.0%
☆
P8-30
Any frequency reaching
detection value 1
0.00 Hz to maximum frequency
50.00Hz
☆
P8-31
Any frequency reaching
detection amplitude 1
0.0%
–100.0% (maximum frequency)
0.0%
☆
P8-32
Any frequency reaching
detection value 2
0.00 Hz to maximum frequency
50.00Hz
☆
P8-33
Any frequency reaching
detection amplitude 2
0.0%
–100.0% (maximum frequency)
0.0%
☆
P8-34
Zero current detection level
0.0%
–300.0% (rated motor current)
5.0%
☆
P8-35
Zero current detection delay
time
0.01s
~
600.00s
0.10s
☆
P8-36
Output over current threshold
0.0% (no detection)
0.1%
–300.0% (rated motor current)
)
200.0%
☆