HV580L Series Frequency Inverter
70
Function
Code
Parameter Name
Setting Range
Default
Property
Group Pd: Communication Parameters
Pd-00
Baud rate
Unit’s digit: MODBUS 0: 300BPS
1: 600BPS
2: 1200BPS
3: 2400BPS
4: 4800BPS
5: 9600BPS
6: 19200BPS
7: 38400BPS
8: 57600BPS
9: 115200BPS
Ten’s digit: Profibus-DP
0: 115200BPs
1: 208300BPs
2: 256000BPs
3: 512000Bps
Hundred’s digit (reserved)
Thousand’s digit: CANlink baud rate
0: 20
1: 50
2: 100
3: 125
4: 250
5: 500
6: 1M
6005
☆
Pd-01
MODBUS Data format
0: No check, data format (8-N-2)
1: Even parity check, data format (8-E-1)
2: Odd parity check, data format (8-O-1)
3: No check, data format (8-N-1) (Valid for
MODBUS)
0
☆