HV580L Series Frequency Inverter
39
Function Code
Parameter Name
Setting Range
Default
Property
P3-08
Multi-point V/F voltage 3
0.0%
~
100.0%
78.0%
★
P3-09
V/F slip compensation gain
0.0%
~
200.0%
0.0%
☆
P3-10
V/F over-excitation gain
0
~
200
64
☆
P3-11
V/F oscillation suppression
gain
0
~
100
Model
dependent
☆
P3-13
Voltage source for V/F
separation
0: Digital setting (P3-14)
1: AI1
2: AI2
3: AI3
4: Pulse setting (X5)
5: Multi-reference
6: Simple PLC
7: PID
8: Communication setting
100.0% corresponds to the rated
motor voltage
0
☆
P3-14
Voltage digital setting for V/F
separation
0 V to rated motor voltage
0V
☆
P3-15
Voltage rise time of V/F
separation
0.0
–1000.0s
It indicates the time for the
voltage rising from 0 V to rated
motor voltage.
0.0s
☆
P3-18
Overcurrent stall prevention
current limit (for VF mode)
100 to 200 (% inverter rated
current)
170
☆
P3-19
Over current stall prevention
enable
0: Disable; 1: Enable
1
☆
P3-20
Over current stall prevention
gain
0 to 100
20
☆