HV580L Series Frequency Inverter
160
P0-10 (Maximum frequency) multiplied by PB-01.
Jump frequency = Swing amplitude AW x PB-02 (Jump frequency amplitude).
• If relative to the central frequency (PB-00 = 0), the jump frequency is a variable value.
• If relative to the maximum frequency (PB-00 = 1), the jump frequency is a fixed value.
The swing frequency is limited by the frequency upper limit and frequency lower limit.
PB-03
Swing frequency cycle
Default
10.0s
Setting range
0.0s
~
3000.0s
PB-04
Triangular wave rising
time coefficient
Default
50.0%
Setting range
0.0%
~
100.0%
PB-03 specifies the time of a complete swing frequency cycle.
PB-04 specifies the time percentage of triangular wave rising time to PB-03 (Swing frequency cycle).
• Triangular wave rising time = PB-03 (Swing frequency cycle) x PB-04 (Triangular wave rising time coefficient,
unit: s)
• Triangular wave falling time = PB-03 (Swing frequency cycle) x (1 – PB-04 Triangular wave rising time
coefficient, unit: s)
PB-05
Setting Length
Default
1000m
Setting range
0m
~
65535m
PB-06
Actual Length
Default
0m
Setting range
0m
~
65535m
PB-07
Pulse/meter
Default
100.0
Setting range
0.1
~
6553.5
The preceding parameters are used for fixed length control.
The length information is collected by DI terminals. PB-06 (Actual length) is calculated by dividing the number
of pulses collected by the DI terminal by PB-07 (Number of pulses each meter).
When the actual length PB-06 exceeds the set length in PB-05, the DO terminal allocated with function 10
(Length reached) becomes ON.
During the fixed length control, the length reset operation can be performed via the DI terminal allocated with
function 28. For details, see the descriptions of P4-00 to P4-09.
Allocate corresponding DI terminal with function 27 (Length count input) in applications. If the pulse frequency
is high, X5 must be used.
PB-08
Set count value
Default
1000
Setting range
1
~
65535
PB-09
Designated count value Default
1000
Setting range
1
~
65535