HV580L Series Frequency Inverter
136
Figure 6-17 Detection range of frequency reached
P8-22
Jump frequency during
acceleration/deceleration
Default
0
Setting Range 0: Disabled; 1: Enabled
It is used to set whether the jump frequencies are valid during acceleration/deceleration.
When the jump frequencies are valid during acceleration/deceleration, and the running frequency is within the
frequency jump range, the actual running frequency will jump over the set frequency jump amplitude (rise
directly from the lowest jump frequency to the highest jump frequency). The following figure shows the
diagram when the jump frequencies are valid during acceleration/deceleration.
Figure 6-18 Diagram when the jump frequencies are valid during acceleration/deceleration
P8-25
Frequency switchover point between
acceleration time 1 and acceleration time 2
Default
0.00Hz
Setting Range
0.00Hz
~
maximum frequency
P8-26
Frequency switchover point between
deceleration time 1 and deceleration time 2
Default
0.00Hz
Setting Range
0.00Hz
~
maximum frequency
This function is valid when motor 1 is selected and acceleration/deceleration time switchover is not performed
by means of X terminal. It is used to select different groups of acceleration/deceleration time based on the
running frequency range rather than DI terminal during the running process of the AC drive.