HV580L Series Frequency Inverter
46
Function
Code
Parameter Name
Setting Range
Default
Property
Group P5: Output Terminals
P5-00
Y2 terminal output mode
0: Pulse output (Y2P)
1: Pulse output (Y2R)
1
☆
P5-01
Y2R function (open collector
output terminal)
Attention!
Set
P5-00 = 1
when used as
MC or Brake output.
0: No output
1: AC drive running
2: Fault output (stop)
3: Frequency-level detection
PDT1 output
4: Frequency reached
5: Zero-speed running (no output
at stop)
6: Motor overload pre-warning
7: AC drive overload pre-warning
8: Set count value reached
9: Designated count value
reached
10: Length reached
11: PLC cycle complete
12: Accumulative running time
reached
13: Frequency limited
14: Torque limited
15: Ready for RUN
16: VS>AS
17: Frequency upper limit
reached
18: Frequency lower limit
reached
(no output at stop)
19: Under voltage state output
20: Communication setting
21: Reserved
22: Reserved
23: Zero-speed running 2 (having
output at stop)
24: Accumulative power-on time
reached
2
☆
P5-02
Relay function (T/A-T/B-T/C)
43
☆
P5-03
Extension card relay function
( P/A-P/B-P/C )
42
☆