Switchover between forward rotation
and reverse rotation
3
Forward JOG
4
Reverse JOG
MF key refers to multifunctional key. You can set the function of the MF key by using this parameter. You can
perform switchover by using this key both in stop or running state.
0: MF key disabled
1: Switchover between operation panel control and remote command control (terminal or communication).
You can perform switchover from the current command source to the operation panel control (local operation).
If the current command source is operation panel control, this key is invalid.
2: Switchover between forward rotation and reverse rotation
You can change the direction of the frequency reference by using the MF key. It is valid only when the current
command source is operation panel control.
3: Forward JOG
You can perform forward JOG (FJOG) by using the MF key.
4: Reverse JOG
You can perform reverse JOG (FJOG) by using the MF key.
P7-02
STOP/RESET key function
Default
1
Setting Range
0
STOP/RESET key enabled only in operation panel
control
1
STOP/RESET key enabled in any operation mode
P7-03
LED display running parameters 1
Default
1F
Setting
Range
0000
~
FFFF
If a parameter needs to be displayed during the running, set the
corresponding bit to 1, and set P7-03 to the hexadecimal equivalent of
this binary number.