HV580L Series Frequency Inverter
104
description of P9-47.
Value
Function
Description
12
Multi-reference terminal 1
The setting of 16 speeds or 16 other references can be
implemented through combinations of 16 states of these four
terminals. For more details, see appendix 1.
13
Multi-reference terminal 2
14
Multi-reference terminal 3
15
Multi-reference terminal 4
16
Terminal 1 for
acceleration/deceleration
time selection
Totally four groups of acceleration/deceleration time can be
selected through combinations of two states of these two
terminals. For more details, see appendix 2.
17
Terminal 2 for
acceleration/deceleration
time selection
18
Frequency source
switchover
The terminal is used to perform switchover between two
frequency sources according to the setting in P0-07.
19
UP/DOWN setting clear
(terminal, operation panel)
If the frequency source is digital setting, the terminal is used to
clear the modification by using the UP/DOWN function or the
increment/decrement key on the operation panel, returning the set
frequency to the value of P0-08.
20
Command source
switchover terminal
If the command source is set to terminal control (P0-02 = 1), this
terminal is used to perform switchover between terminal control
and operation panel control.
If the command source is set to communication control (P0-02 =
2), this terminal is used to perform switchover between
communication control and operation panel control.
21
Acceleration/Deceleration
prohibited
It enables the AC drive to maintain the current frequency output
without being affected by external signals (except the STOP
command).
22
PID pause
PID is invalid temporarily. The AC drive maintains the current
frequency output without supporting PID adjustment of frequency
source.