HV580L Series Frequency Inverter
119
15
Ready for RUN
If the AC drive main circuit and control circuit become
stable, and the AC drive detects no fault and is ready for
RUN, the terminal becomes ON.
16
VS>AS
When the input of AI1 is larger than the input of AI2, the
terminal becomes ON.
17
Frequency upper limit
Reached
If the running frequency reaches the upper limit, the
terminal becomes ON.
18
Frequency lower limit
reached (no output at
stop)
If the running frequency reaches the lower limit, the
terminal becomes ON. In the stop state, the terminal
becomes OFF.
19
Undervoltage state output
If the AC drive is in undervoltage state, the terminal
becomes ON.
20
Communication setting
Refer to the communication protocol.
21
Reserved
Reserved.
22
Reserved
Reserved.
Value
Function
Description
23
Zero-speed running 2
(having output at stop)
If the output frequency of the AC drive is 0, the terminal
becomes ON. In the state of stop, the signal is still ON.
24
Accumulative power-on time
reached
If the AC drive accumulative power-on time (P7-13)
exceeds the value set in P8-16, the terminal becomes
ON.
25
Frequency level
detection FDT2 output
Refer to the descriptions of P8-28 and P8-29.
26
Frequency 1 reached
Refer to the descriptions of P8-30 and P8-31.
27
Frequency 2 reached
Refer to the descriptions of P8-32 and P8-33.
28
Current 1 reached
Refer to the descriptions of P8-38 and P8-39.
29
Current 2 reached
Refer to the descriptions of P8-40 and P8-41.
30
Timing reached
If the timing function (P8-42) is valid, the terminal becomes ON
after the current running time of the AC drive reaches the set
time.
31
VS input limit exceeded
If AI1 input is larger than the value of P8-46 (AI1 input
voltage upper limit) or lower than the value of P8-45 (AI1
input voltage lower limit), the terminal becomes ON.
32
Load becoming 0
If the load becomes 0, the terminal becomes ON.