These parameters are used to set the relationship between X5 pulse input and corresponding settings. The
pulses can only be input by X5. The method of setting this function is similar to that of setting VS 1function.
P4-33
VS curve selection
Default
321
Setting Range
Unit's digit
VS curve selection
1
Curve 1
(
2 points, see P4-13
~
P4-16
)
2
Curve 2
(
2 points, see P4-18
~
P4-21
)
3
Curve 3
(
2 points, see P4-23
~
P4-26
)
4
Curve 4
(
4 points, see A6-00
~
A6-07
)
5
Curve 5
(
4 points, see A6-08
~
A6-15
)
Ten's digit
AS curve selection
(
1
~
5, same to VS1
)
Hundred's digit
VS2 curve selection
(
1
~
5, same to VS1
)
The unit's digit, ten's digit and hundred's digit of this parameter are respectively used to select the
corresponding curve of VS1, AS and VS2. Any of the five curves can be selected for VS1, AS and VS2.
Curve 1, curve 2 and curve 3 are all 2-point curves, set in group P4. Curve 4 and curve 5 are both 4-point
curves, set in group A6.
The HV580L provides two AI terminals as standard. VS2 is provided by an optional extension card.
P4-34
Setting for VS less than minimum
input
Default
000
Setting Range
Unit's digit
Setting for VS1 less than minimum input
0
Minimum value
1
0.0%
Ten's digit
Setting for AS less than minimum input
(
0
~
1
,
same to VS1
)
Hundred's digit
Setting for VS2 less than minimum input
(
0
~
1
,
same to VS1
)
This parameter is used to determine the corresponding setting when the analog input voltage is less than the
minimum value. The unit's digit, ten's digit and hundred's digit of this parameter respectively correspond to the
setting for VS2, AS and VS2.
If the value of a certain digit is 0, when analog input voltage is less than the minimum input, the corresponding
setting of the minimum input (P4-14, P4-19, P4-24) is used.
If the value of a certain digit is 1, when analog input voltage is less than the minimum input, the corresponding
value of this analog input is 0.0%.
P4-35
X1 delay time
Default
0.0s
Setting Range
0.0s
~
3600.0s