1008H
DI input status
1018H
AI3 voltage before correction
1009H
DO output status
1019H
Line speed
100AH
AI1 voltage
101AH
Current power on time
100BH
AI2 voltage
101BH
Current running time
100CH
Running speed
101CH
PULSE input pulse frequency, unit
1Hz
100DH
DI input status
101DH
Communication setup value
100EH
DO output status
101EH
Actual feedback speed
100FH
AI1 voltage
101FH
Main frequency X display
–
–
1020H
Auxiliary frequency Y display
Caution:
The communication setup value is percentage of the relative value, 10000 corresponds to 100.00%
,
-10000
corresponds to -100.00%. For data of dimensional frequency, the percentage value is the percentage of the
maximum frequency. For data of dimensional torque, the percentage is P2.10, A2.48, A3.48, A4.48 (Torque
upper digital setup, corresponding to the first, second, third, fourth motor).
Control command input to the inverter (write-only)
Command word address
Command function
2000H
0001
:
Forward operation
0002
:
Reverse operation
0003
:
Forward jog
0004
:
Reverse jog
0005
:
Free stop
0006
:
Speed-down stop
0007
:
Fault reset
Read inverter status
:
(read-only)
Status word address
Status word function
3000H
0001
:
Forward operation
0002
:
Reverse operation
0003
:
Stop