HV580L Series Frequency Inverter
76
0
:
Operation panel control channel (
―LOCAL/REMOT‖ indicator off)
Commands are given by pressing keys ―RUN‖ and ―STOP/RES‖ on the operation panel
1
:
Terminal control (
―LOCAL /REMOT‖ indicator on)
Commands are given by means of multifunctional input terminals with functions such as FWD, REV, JOGF,
and JOGR.
2
:
Communication control channel (
―LOCAL/REMOT‖ indicator blinking)
Commands are given from host computer. If this parameter is set to 2, a communication card (Modbus RTU,
PROFIBUS-DP card, CANlink card, user programmable card or CANopen card) must be installed
Related to the communication function parameters, please see the "PD group communication parameters"
instructions, and reference the corresponding communication card, the appendix of this manual contains brief
explanation of communication card.
P0-03
Main frequency source X
selection
Default
0
Setting Range
0
Digital setting ( Preset frequency P0-08, UP/DOWN
revisable, non-retentive at power failure)
1
Digital setting (Preset frequency P0-08, UP/DOWN revisable,
retentive at power failure)
2
VS
3
AS
4
VS2
5
Pulse setting (X5)
6
Multi-reference
7
PLC
8
PID
9
Communication setting
It is used to select the setting channel of the main frequency. You can set the main frequency in the following
10 channels:
0: Digital setting (non-retentive at power failure)
The initial value of the set frequency is the value of P0-08 (Preset frequency). You can change the set
frequency by pressing ▲ and ▼ on the operation panel (or using the UP/DOWN functions of input terminals).
When the AC drive is powered on again after power failure, the set frequency reverts to the value of P0-08.
1: Digital setting (retentive at power failure)
The initial value of the set frequency is the value of P0-08 (Preset frequency). You can change the set
frequency by pressing keys ▲ and ▼ on the operation panel (or using the UP/DOWN functions of input