HV580L Series Frequency Inverter
112
P4-15
VS curve 1 maximum input
Default
10.00V
Setting Range
P4-13
~
10.00V
P4-16
Corresponding setting of VS
curve 1 maximum input
Default
100.0%
Setting Range
-100.00%
~
100.0%
P4-17
VS1 filter time
Default
0.10s
Setting Range
0.00s
~
10.00s
These parameters are used to define the relationship between the analog input voltage and the corresponding
setting.
When the analog input voltage exceeds the maximum value (P4-15), the maximum value is used. When the
analog input voltage is less than the minimum value (P4-13), the value set in P4-34 (Setting for VS less than
minimum input) is used.
When the analog input is current input, 1 mA current corresponds to 0.5 V voltages.
P4-17 (VS 1 filter time) is used to set the software filter time of VS. If the analog input is liable to interference,
increase the value of this parameter to stabilize the detected analog input. However, increase of the AI filter
time will slow the response of analog detection. Set this parameter properly based on actual conditions.
In different applications, 100% of analog input corresponds to different nominal values. For details, refer to the
description of different applications.
Two typical setting examples are shown in the following figure.