HV580L Series Frequency Inverter
105
23
PLC pause
The terminal is used to restore the original status of PLC control
for the AC drive when PLC control is started again after a pause.
24
Swing pause
The AC drive outputs the central frequency, and the swing
frequency function pauses.
25
Counter input
This terminal is used to count pulses.
26
Counter reset
This terminal is used to clear the counter status.
27
Length count input
This terminal is used to count the length.
28
Length reset
This terminal is used to clear the length.
29
Torque control prohibited The AC drive is prohibited from torque control and enters the
speed control mode.
30
Pulse input (enabled only
for X5)
X5 is used for pulse input.
31
Reserved
Reserved
32
Immediate DC braking
After this terminal becomes ON, the AC drive directly switches
over to the DC braking state.
33
Normally closed (NC) input
of external fault
After this terminal becomes ON, the AC drive reports
Err15 and stops.
34
Frequency modification
forbidden
After this terminal becomes ON, the AC drive does not respond to
any frequency modification.
35
Reverse PID action
direction
After this terminal becomes ON, the PID action direction is
reversed to the direction set in PA-03.
36
External STOP terminal 1
In operation panel mode, this terminal can be used to stop the AC
drive, equivalent to the function of the STOP key on the operation
panel.
37
Command source
switchover terminal 2
It is used to perform switchover between terminal control and
communication control. If the command source is terminal control,
the system will switch over to communication control after this
terminal becomes ON.
38
PID integral pause
After this terminal becomes ON, the integral adjustment function
pauses. However, the proportional and differentiation adjustment
functions are still valid.