HV580L Series Frequency Inverter
117
P5-00
Y2 terminal output mode Default
0
Setting Range
0
Pulse output (Y2P)
1
Switch signal output (Y2R)
The Y2 terminal is programmable multiplexing terminal. It can be used for high-speed pulse output (Y2P), with
maximum frequency of 100 kHz. Refer to P5-06 for relevant functions of Y2P. It can also be used as open
collector switch signal output (Y2R).
P5-01
Y2R function (open-collector output terminal)
Default
0
P5-02
Relay function (T/A-T/B-T/C)
Default
2
P5-03
Extension card relay function (P/A-P/B-P/C)
Default
0
P5-04
Y1 function selection (open-collector output terminal) Default
1
P5-05
Extension card Y2 function
Default
4
These five parameters are used to select the functions of the five digital output terminals. T/A-T/B-T/C and
P/A-P/B-P/C are respectively the relays on the control board and the extension card.
The functions of the output terminals are described in the following table.
Value
Function
Description
0
No output
The terminal has no function.
1
AC drive running
When the AC drive is running and has output frequency
(can be zero), the terminal becomes ON.
2
Fault output (stop)
When the AC drive stops due to a fault, the terminal
becomes ON.
3
Frequency-level detection
FDT1 output
Refer to the descriptions of P8-19 and P8-20.
4
Frequency reached
Refer to the descriptions of P8-21.
5
Zero-speed running
(no output at stop)
If the AC drive runs with the output frequency of 0, the
terminal becomes ON. If the AC drive is in the stop state,
the terminal becomes OFF.