HV580L Series Frequency Inverter
87
Setting Range
0.01A
~
655.35A( AC drive power <=55kW)
0.1A
~
6553.5A( AC drive power >55kW)
P1-04
Rated motor frequency Default
Model dependent
Setting Range
0.01Hz
~
maximum frequency
P1-05
Rated motor rotational
speed
Default
Model dependent
Setting Range
1rpm
~
65535rpm
Set the parameters according to the motor nameplate, no matter whether V/F control or vector control is adopted.
To achieve better V/F or vector control performance, motor auto-tuning is required. The motor auto-tuning
accuracy depends on the correct setting of motor nameplate parameters.
P1-06
Stator resistance
(asynchronous motor)
Default
Model dependent
Setting Range
0.001Ω
~
65.535Ω(AC drive power ≤ 55kW)
0.0001Ω
~
6.5535Ω(AC drive power >55kW)
P1-07
Rotor resistance
(asynchronous motor)
Default
Model dependent
Setting Range
0.001Ω
~
65.535Ω(AC drive power ≤ 55kW)
0.0001Ω
~
6.5535Ω(AC drive power >55kW)
P1-08
Leakage inductive
reactance (asynchronous
motor)
Default
Model dependent
Setting Range
0.01mH
~
655.35mH(AC drive power ≤ 55kW)
0.001mH
~
65.535mH(AC drive power >55kW)
P1-09
Mutual inductive
reactance
(asynchronous motor)
Default
Model dependent
Setting Range
0.1mH
~
6553.5mH(AC drive power ≤ 55kW)
0.01mH
~
655.35mH(AC drive power >55kW)
P1-10
No-load current
(asynchronous motor)
Default
Model dependent