HV580L Series Frequency Inverter
65
Function
Code
Parameter Name
Setting Range
Default
Property
PA-13
PID output filter time
0.00
~
60.00s
0.00s
☆
PA-14
Reserved
-
-
☆
PA-15
Proportional gain Kp2
0.0
~
100.0
20.0
☆
PA-16
Integral time Ti2
0.01s
~
10.00s
2.00s
☆
PA-17
Differential time Td2
0.000s
~
10.000s
0.000s
☆
PA-18
PID parameter switchover
condition
0: No switchover
1: Switchover via DI
2
:
Automatic switchover based on
Deviation
0
☆
PA-19
PID parameter switchover
deviation 1
0.0%
~
PA-20
20.0%
☆
PA-20
PID parameter switchover
deviation 2
PA-19
~
100.0%
80.0%
☆
PA-21
PID initial value
0.0%
~
100.0%
0.0%
☆
PA-22
PID initial value holding time
0.00
~
650.00s
0.00s
☆
PA-23
Maximum deviation between
two PID outputs in forward
direction
0.00%
~
100.00%
1.00%
☆
PA-24
Maximum deviation between
two PID outputs in reverse
direction
0.00%
~
100.00%
1.00%
☆
PA-25
PID integral property
Unit's digit (Integral separated)
0: Invalid 1: Valid
Ten's digit (Whether to stop integral
operation when the output reaches the
limit)
0: Continue integral operation
1: Stop integral operation
00
☆
PA-26
Detection value of PID feedback
loss
0.0%
:
Not judging feedback loss
0.1%
~
100.0
%
0.0%
☆
PA-27
Detection time of PID feedback
loss
0.0s
~
20.0s
0.0s
☆
PA-28
PID operation at stop
0: No PID operation at stop
1: PID operation at stop
0
☆