HV580L Series Frequency Inverter
83
Setting Range
0.00s
~
650.00s (P0-19=2)
0.0s
~
6500.0s (P0-19=1)
0s
~
65000s(P0-19=0)
Acceleration time indicates the time required by the AC drive to accelerate from 0 Hz to
"Acceleration/Deceleration base frequency" (P0-25), that is, t1 in Figure 6-1.
Deceleration time indicates the time required by the AC drive to decelerate from
"Acceleration/Deceleration base frequency" (P0-25) to 0 Hz, that is, t2 in Figure 6-1.
Figure 6-1 Acceleration / Deceleration time
The HV580L provides totally four groups of acceleration/deceleration time for selection. You can perform
switchover by using a X terminal.
Group 1: P0-17, P0-18
Group 2: P8-03, P8-04
Group 3: P8-05, P8-06
Group 4: P8-07, P8-08
P0-19
Acceleration/Deceleration
time unit
Default
1
Setting Range
0
1s
1
0.1s
2
0.01s
To satisfy requirements of different applications, the HV580L provides three acceleration/deceleration time
units, 1s, 0.1s and 0.01s.
Note:
Modifying this parameter will make the displayed decimal places change and corresponding