HV580L Series Frequency Inverter
90
P1-32
U, V, W phase sequence of
UVW
encoder
Default
0
Setting Range
0
Forward
1
Reverse
P1-33
UVW encoder angle offset
Default
0.0°
Setting Range
0.0°
~
359.9°
These two parameters are valid only when the UVW encoder is applied to a synchronous motor.
They can be obtained by synchronous motor no-load auto-tuning or with-load auto tuning. After installation of
the synchronous motor is complete, the values of these two parameters must be obtained by motor
auto-tuning. Otherwise, the motor cannot run properly.
P1-34
Number of pole pairs of
resolver
Default
1
Setting Range
1
~
65535
If a resolver is applied, set the number of pole pairs properly.
P1-36
Encoder wire-break fault detection time
Default
0.0s
Setting Range
0.0s: No action
0.1s
~
10.0s
This parameter is used to set the time that a wire-break fault lasts. If it is set to 0.0s, the AC drive does not
detect the encoder wire-break fault.
If the duration of the encoder wire-break fault detected by the AC drive exceeds the time set in this parameter,
the AC drive reports Err20.
P1-37
Auto-tuning selection
Default
0
Setting
0
No auto-tuning
1
Asynchronous motor static auto-tuning
2
Asynchronous motor complete auto-tuning
3
Static complete parameter identification
11
Synchronous motor with-load auto-tuning
12
Synchronous motor no-load auto-tuning
0: No auto-tuning, auto-tuning is prohibited.
1: Asynchronous motor static auto-tuning