HV580L Series Frequency Inverter
200
Pd-04
Communication overtime Default
0.0 s
Setting range
0.0 s (invalid); 0.1~60.0s
When the function set to 0.0s, the communication overtime parameter is invalid.
When the function code is set to valid value, if the interval time between one communication with the next
communication exceeded the communications overtime, the system will report communication fault error (fault
serial 16= E.CoF1) . Under normal circumstances, it will be set to invalid value. If the system of continuous
communication, setting parameters, you can monitor the communication status.
Pd-05
Communication protocol
selection
Default
0
Setting range
0: non standard Modbus protocal
1: Standard Modbus Protocal
Pd.05=1: Select Standard Modbus protocol.
Pd.05=0: Reading command, the slave returns the number of bytes which has one more byte than the
standard Modbus protocol, for specific please refer to the protocol, the part of the "5 communication data
structure‖.
Pd-06
Communication read the
current resolution
Default
0
Setting range
0: 0.01A; 1: 0.1A
To determine when the communication reads the output current, what the output current value unit is.