HV580L Series Frequency Inverter
38
Function
Code
Parameter Name
Setting Range
Default
Property
P2-20
Maximum field weakening
current
1%
~
300%
50%
☆
P2-21
Field weakening automatic
adjustment gain
10%
~
500%
100%
☆
P2-22
Field weakening integral
multiple
2
~
10
2
☆
Group P3: V/F Control Parameters
P3-00
V/F curve setting
0: Linear V/F
1: Multi-point V/F
2: Square V/F
3: 1.2-power V/F
4: 1.4-power V/F
6: 1.6-power V/F
8: 1.8-power V/F
9: Reserved
10: V/F complete separation
11: V/F half separation
0
★
P3-01
Torque boost
0.0% (fixed torque boost)
0.1%
–30.0%
Model
dependent
☆
P3-02
Cut-off frequency of torque
boost
0.00 Hz to maximum output
frequency
50.00Hz
★
P3-03
Multi-point V/F frequency 1
0.00Hz
~
P3-05
10.00Hz
★
P3-04
Multi-point V/F voltage 1
0.0%
~
100.0%
28.0%
★
P3-05
Multi-point V/F frequency 2
P3-03
~
P3-07
25.00Hz
★
P3-06
Multi-point V/F voltage 2
0.0%
~
100.0%
55.0%
★
P3-07
Multi-point V/F frequency 3
P3-05 to rated motor frequency
(P1-04)