Chapter 3 Mechanical and Electrical Installation
3.1 Mechanical Installation
3.1.1 Installation Environment Requirements
1. Ambient temperature -10
℃~
40
℃,
Well ventilated or indoor Spaces with ventilation devices, more than
40
℃
derating use. Avoid vibration, direct sunlight, away from heat source.
2. AC drives can install where altitude 1000 m below the output rated power, when more than 1000 m altitude
need derating use, specific derating range, please contact the company.
3. Avoid high temperature high humidity, the humidity is less than 90% RH (Non-condensate).
4. Apart from the oil, salt and corrosive gas. To prevent water, steam, dust, lint, metal powder.
5. Prevent electromagnetic interference, away from the interference sources.
6. It is prohibited to use in flammable, explosive gas, liquid or solid dangerous environment.
3.1.2 Installation Clearance Requirements
The clearance that needs to be reserved varies with the power class of the HV580L, as shown in the following
figure.
The HV580L series AC drive dissipates heat from the bottom to the top. When multiple AC drives are required
to work together, install them side by side.
For application installing multiple AC drives, if one row of AC drives need to be installed above another row,
install an insulation guide plate to prevent AC drives in the lower row from heating those in the upper row and
causing faults.