HV580L Series Frequency Inverter
108
ON
OFF
Acceleration/Deceleration time 3
P8-05
、
P8-06
ON
ON
Acceleration/Deceleration time 4
P8-07
、
P8-08
Appendix 3: State combinations of two motor selection terminals
Terminal 2
Terminal 1
Selected Motor
Corresponding Parameters
OFF
OFF
Motor 1
Group P1, P2
OFF
ON
Motor 2
Group A2
ON
OFF
Motor 3
Group A3
ON
ON
Motor 4
Group A4
P4-10
X filter time
Default
0.010s
Setting Range
0.000s
~
1.000s
It is used to set the software filter time of X terminal status. If X terminals are liable to interference and may
cause malfunction, increase the value of this parameter to enhance the anti-interference capability. However,
increase of X filter time will reduce the response of X terminals.
P4-11
Terminal command mode Default
0
Setting Range
0
Two-line mode 1
1
Two-line mode 2
2
Three-line mode 1
3
Three-line mode 2
This parameter is used to set the mode in which the AC drive is controlled by external terminals.
0: Two-line mode 1: It is the most commonly used two-line mode, in which the forward/reverse rotation of the
motor is decided by X1 and X2. The parameters are set as below:
Function Code
Parameter Name
Value
Function Description
P4-11
Terminal command mode 0
Two-line 1
P4-00
X1 function selection
1
Forward RUN (FWD)
P4-01
X2 function selection
2
Reverse RUN (REV)