HV580L Series Frequency Inverter
139
P8-36
Output overcurrent threshold
Default
200.0%
Setting Range
0.0%( no detection );0.1%
~
300.0%
(
rated motor
current
)
P8-37
Output overcurrent detection
delay time
Default
0.00s
Setting Range
0.00s
~
600.00s
If the output current of the AC drive is equal to or higher than the overcurrent threshold and the duration
exceeds the detection delay time, the corresponding DO becomes ON. The output overcurrent detection
function is shown in the following figure.
Figure 6-22 Output overcurrent detection
P8-38
Any current reaching 1
Default
100.0%
Setting Range
0.0%
~
300.0%( rated motor current )
P8-39
Any current reaching 1 amplitude Default
0.0%
Setting Range
0.0%
~
300.0%( rated motor current )
P8-40
Any current reaching 2
Default
100.0%
Setting Range
0.0%
~
300.0%( rated motor current )
P8-41
Any current reaching 2 amplitude Default
0.0%
Setting Range
0.0%
~
300.0%( rated motor current )