HV580L Series Frequency Inverter
147
2
Switch over to V/F control, continue to run
Ten's digit
EEPROM read-write fault (Err21)
0
Coast to stop
1
Stop according to the stop mode
Hundred's digit
Reserved
Thousand's digit
Motor overheat (Err25)
Same as unit's digit in P9-47
Ten thousand's digit
Accumulative running time reached (Err26) Same
as unit's digit in P9-47
P9-49
Fault protection action selection 3
Default
00000
Setting Range
Unit's digit
User-defined fault 1(Err27)
Same as unit's digit in P9-47
Ten's digit
User-defined fault 2(Err28)
Same as unit's digit in P9-47
Hundred's digit
Accumulative power-on time reached (Err29) Same
as unit's digit in P9-47
Thousand's digit
Load becoming 0 (Err30)
0
Coast to stop
1
Stop according to the stop mode
2
Continue to run at 7% of rated motor frequency
and resume to the set frequency if the load
Recovers
Ten thousand's digit
PID feedback lost during running (Err31) Same as
unit's digit in P9-47