HV580L Series Frequency Inverter
122
P5-20
Y1 output delay time
Default
0.0s
Setting Range
0.0s
~
3600.0s
P5-21
DO2 output delay time
Default
0.0s
Setting Range
0.0s
~
3600.0s
These parameters are used to set the delay time of output terminals Y2R, relay 1, relay 2, Y1 and DO2 from
status change to actual output.
P5-22
DO valid mode selection
Default
00000
Setting Range
Unit's digit
Y2R valid mode
0
Positive logic
1
Negative logic
Ten's digit
RELAY1 valid mode(0
~
1, same as Y2R)
Hundred's digit
RELAY2 valid mode(0
~
1, same as Y2R)
Thousand's digit
Y1 valid mode(0
~
1, same as Y2R)
Ten thousand's digit Y2 valid mode(0
~
1, same as Y2R)
It is used to set the logic of output terminals Y2R, relay 1, relay 2, Y1 and Y2.
0: Positive logic
The output terminal is valid when being connected with COM, and invalid when being disconnected from COM.
1: Negative logic
The output terminal is invalid when being connected with COM, and valid when being disconnected from COM
Group P6 Start/Stop Control
P6-00
Start mode
Default
0
Setting Range
0
Direct start
1
Rotational speed tracking restart
2
Pre-excited start (asynchronous motor)
0: Direct start
– If the DC braking time is set to 0, the AC drive starts to run at the startup frequency.
– If the DC braking time is not 0, the AC drive performs DC braking first and then starts to run at the startup
frequency. It is applicable to small-inertia load application where the motor is likely to rotate at startup.
1: Rotational speed tracking restart
The AC drive judges the rotational speed and direction of the motor first and then starts at the tracked
frequency. Such smooth start has no impact on the rotating motor. It is applicable to the restart upon
instantaneous power failure of large-inertia load. To ensure the performance of rotational speed tracking
restart, set the motor parameters in group P1 correctly.
2: Pre-excited start (asynchronous motor)