HV580L Series Frequency Inverter
57
P8-56
Brake release frequency
threshold
0.00 to 25.00Hz
0Hz
☆
P8-57
Brake release delay ON set
time
0.0 to 5.0 sec 0.1
0.0 to 5.0s
0.1s
☆
P8-58
Brake apply frequency
threshold
0.00 to 25.00Hz
0.50Hz
☆
P8-59
Brake apply delay OFF set
time
0.0 to 5.0s
0.2s
☆
P8-60
Drive run delay ON set time
0.00 to 10.00s
0.2s
☆
P8-61
MC contactor delay OFF set
time
0.00 to 10.00s
0.2s
☆
Function
Code
Parameter Name
Setting Range
Default
Property
Group P9: Fault and Protection
P9-00
Motor overload protection
selection
0: Disabled
1: Enabled
1
☆
P9-01
Motor overload protection gain 0.20
~
10.00
1.00
☆
P9-02
Motor overload warning
coefficient
50%
~
100%
80%
☆
P9-03
Overvoltage stall gain
0
~
100
0
☆
P9-04
Overvoltage stall protective
voltage
120%
~
150%
130%
☆
P9-05
Overcurrent stall gain
0
~
100
20
☆
P9-06
Overcurrent stall protective
current
100%
~
200%
150%
☆
P9-07
Short-circuit to ground upon
power-on
0: Disabled
1: Enabled
1
☆
P9-09
Fault auto reset times
0
~
20
0
☆