HV580L Series Frequency Inverter
144
P9-09
Fault auto reset times
Default
0
Setting Range
0
~
20
It is used to set the times of fault auto resets if this function is used. After the value is exceeded, the AC drive
will remain in the fault state.
P9-10
DO action during fault auto reset
Default
0
Setting Range
0: Not act; 1: Act
It is used to decide whether the DO acts during the fault auto reset if the fault auto reset function is selected.
P9-11
Time interval of fault auto reset Default
1.0s
Setting Range
0.1s
~
100.0s
It is used to set the waiting time from the alarm of the AC drive to fault auto reset.
P9-12
Input phase loss
protection/contactor energizing
protection selection
Default
11
Setting Range
Unit's digit: Input phase loss protection
Ten's digit: Contactor energizing
0: Disabled
1: Enabled
It is used to determine whether to perform input phase loss or contactor energizing protection.
For every voltage class, the HV580L AC drives of powers equal to or greater than those listed in the preceding
table provide the function of input phase loss or contactor energizing protection. The HV580L AC drives below
the power listed in the table do not have the function no matter whether P9-12 is set to 0 or 1.
P9-13
Output phase loss protection selection Default
1
Setting Range
0: Disabled 1: Enabled
It is used to determine whether to perform output phase loss protection.
P9-14
1st fault type
0
~
99
P9-15
2nd fault type
P9-16
3rd (latest) fault type
It is used to record the types of the most recent three faults of the AC drive. 0 indicates no fault. For possible
causes and solution of each fault, refer to Chapter 8.
P9-17
Frequency upon 3rd fault
It displays the frequency when the latest fault occurs.
P9-18
Current upon 3rd fault
It displays the current when the latest fault occurs.