HV580L Series Frequency Inverter
198
Inverter fault description
:
Inverter fault address
Inverter fault information
8000H
0000
:
No fault
0001
:
Reserved
0002
:
Speed-up over current
0003
:
Speed-down over current
0004
:
Constant speed over current
0005
:
Speed-up over voltage
0006
:
Speed-down over voltage
0007
:
Constant speed over voltage
0008
:
Buffer resistance overload
fault
0009
:
Under-voltage fault
000A
:
Inverter overload
000B
:
Motor overload
000C
:
Input phase lost
000D
:
Output phase lost
000E
:
Module overheating
000F
:
External fault
0010
:
Communication fault
0011
:
Contactor fault
0012
:
Current detection fault
0013
:
Motor tuning fault
0014
:
Encoder/PG card fault
0015
:
Parameter read and write fault
0016
:
Inverter hardware fault
0017
:
Motor earthing short-circuit
fault
0018
:
Reserved
0019
:
Reserved
001A
:
Running time arrive fault
001B
:
User defined fault 1
001C
:
User defined fault 2
001D
:
Power on time arrive fault
001E
:
Load off
001F
:
PID feedback lost during
operation
0028
:
Fast current limit timeout fault
0029
:
Motor shifting fault during
operation
002A
:
Excessive speed deviation
002B
:
Motor over speed
002D
:
Motor over-temperature
005A
:
Encoder line number setup
fault
005B
:
Encoder not connected
005C
:
Initial position error
005E
:
Speed feedback fault